Definition: The bus whose voltage and frequency remain constant even after the variation in the load is known as the infinite bus. The alternators operating in parallel in a power system are the example of the infinite bus. The on and off of any of the alternators will not affect the working of the power system.
The capacity of a parallel operating system is enormous, their voltage and frequency remain constant even after the disturbance of the load. The connection and disconnection of any of the machines will not affect the magnitude and phase of voltage and frequency of an infinite bus. In an infinite bus system
- The voltage and frequency always remain constant.
- The synchronous impedance of the bus is low because of the parallel operations of the machine.
Synchronous machine on Infinite Bus
The performance of the synchronous machine varies on the infinite bus. When the synchronous machine operates independently, variation in their excitation causes the changes in their terminal voltage. The power factor of the synchronous machine depends only on their load. But when the synchronous machines are operating in parallel, the change in their excitation changes the power factor of the load.
Obtaining an Infinite Bus
Consider generators G1, G2, G3……Gn connected to an infinite bus as shown in the figure below:
Proof of Voltage Remaining Constant
Let,
- V be the terminal voltage of the bus,
- E be the induced emf of each generator,
- ZS is the synchronous impedance of each generator,
- n is the number of generators in parallel
When n is very large ZSeq → 0 and, therefore, I ZSeq → 0
Therefore, V = E (constant)
If the number of alternators operating in parallel is infinite only then ZS = 0
Proof of Frequency Remaining Constant
Let, J be the moment of inertia of each alternator
The total moment of inertia of all n alternators is given as: If the value of n is very large, nJ is also very large.
Therefore, acceleration → 0, and the speed is constant.
The above equation shows that the constant voltage and frequency of the bus depend on the number of machines operating parallel.
thank you very much for your good and useful information I hope for you all the best
thanks
Ismat Mansour
thank you so much for the great explanation